DR-75-24
75W DIN-Rail 24 VDC Power Supply

Specifications | Ordering info | PDF Datasheet Download |

Overview
 

The DR series of power supplies provides a reliable DC power source for any industrial control system. Combining rugged, compact enclosures, incorporating all international standards and approvals, and offering short circuit, over load, over voltage, and over temperature protection, the DR series makes your power supply choice a simple one.

These high quality power supplies have passed a 100% full load burn-in test, and are UL/CUL listed, TUV/CB certified, and CE marked. Models are available with output ratings from 45W to 120W, with 24 VDC output . Customers can choose from a full range of input voltages (85 to 264 VAC and 120 to 370 VDC compatible) making the DR series unbeatable.




Features
 
  • Universal AC input (85 to 264 VAC)
  • DC compatible input (120 to 370 VDC)
  • CE marked and UL508 listed
  • Certified to TUV EN60950
  • Simple snap-on for TS35/7.5 or TS35/15 DIN-Rail
  • 100% full load burn-in test
  • Free air cooling convection
  • Built in EMI filter and low ripple noise
  • 105°C output capacitor
  • Short circuit, overload, over voltage protected

   


Benefits
 
  • Economical and reliable DC power source for industrial devices
  • Design for use in harsh industrial environm


Applications
 
  • Factory automation
  • Transportation automation
  • Utility automation
  • Building automation
Specifications
Input
Input voltage 85-264VAC or 120-370VDC
Input frequency 47-63 Hz
Input current 2.0A/115VAC or 1.2A/230VAC

Output
DC output power 76.8 W
Output voltage 24 VDC
Output V. tolerance ±1%
Output rated current 3.2A
Output current range 0-3.2A
Ripple and noise 150mVp-p
Line regulation ±0.5%
Load regulation ±1%
Efficiency 80%
DC voltage adjust 24-28V
Setup, rise and hold up time 1000ms, 60ms, 50ms/230V
1800ms, 60ms, 10ms/115V

Regulatory Approval
Safety standards TUV EN60950, UL508 Approved
EMC standards CISPR22 (EN55022) CLASS B,
EN61000-4-2,3,4,5,6,8,11; ENV50204,
EN61000-3-2,-3, EN50082-2

Operating protection
Inrush current Cold start at 30A/115V or 60A/230V
Leakage current < 1 mA / 240 VAC
Withstand voltage Between input and output 3 KVAC
Between input and frame ground: 1.5 KVAC
Between output to frame ground: 0.5 KVAC
Isolation resistance Between input and output/input and frame ground/ output and frame ground: 500 VDC/100 Ohms
Overload protection 105 - 150% Type: Constant Current Limiting. Reset: Auto Recovery
Over voltage protection 29 - 34 VDC
Over temperature protection 85°C±5°C
Type: Power shutdown
Reset: Auto Recovery (TSW1)

Mechanical
Dimensions
(W x H x D)
55.5 x 125.2 x 100 mm
Weight (kg) 0.55

Environment
Working temp. and humidity -10°C to 60°C
20 to 90% RH
Temp. coefficient ±0.03% (0-50°C)
Storage temp. and humidity -20°C to 85°C, 10 to 95% RH
Vibration 10-500 Hz, 2G 10 min./1cycle, Period for 60 min. Each Axis
3-year warranty Solid 3-year warranty backed by experienced and friendly technical support personnel


Ordering Information
DR-75-24
  • 75W/3.2A DIN-Rail 24 VDC Power Supply with universal 85 to 264 VAC input